Standard functions
|
Maximum frequency
|
Vector contro: 0~300Hz; V/F control: 0~3200Hz
|
|
Carrier frequency
|
0.5kHz~16kHz
The carrier frequency is automatically adjusted based on the load features.
|
|
Input frequency
resolution
|
Digital setting: 0.01Hz
Analog setting: maximum frequency x 0.025%
|
|
Control mode
|
• Sensorless flux vector control (SFVC)
• Closed-loop vector control (CLVC)
• Voltage/Frequency (V/F) control
|
|
Starting torque
|
• G type: 0.5 Hz/150% (SFVC); 0 Hz/180% (CLVC)
• P type: 0.5 Hz/100%
|
|
Basic functions
|
Speed range
|
1:100 (SFVC)
|
1:1000 (CLVC)
|
|
Constant-speed accuracy
|
± 0.5% (SFVC)
|
± 0.02% (CLVC)
|
|
Torque control
accuracy.
|
± 5% (CLVC)
|
|
Overload capacity
|
• G type: 60s for 150% of the rated current, 3s for 180% of the rated current
• P type: 60s for 120% of the rated current, 3s for 150% of the rated current
|
|
Torque boost
|
•Fixed boost
• Customized boost 0.1%–30.0%
|
|
V/F curve
|
• Straight-line V/F curve
• Multi-point V/F curve
•N-power V/F curve (1.2-power, 1.4-power, 1.6-power, ,1.8-power, square)
|
|
V/F separation
|
Two types: complete separation; half separation
|
|
Acceleration /deceleration curve
|
•Straight-line ramp
• S-curve ramp
Four groups of acceleration/deceleration time with the range of 0.0–6500.0s
|
|
DC braking.
|
DC braking frequency: 0.00Hz~maximum frequency
Braking time: 0.0s~36.0s
Braking action current value: 0.0%–100.0%
|
|
JOG control
|
JOG frequency range: 0.00–50.00 Hz
JOG acceleration/deceleration time: 0.0–6500.0s
|
|
Simple PLC and
multi-speed operation
|
It implements up to 16 speeds via the simple PLC function or combination of DI terminal states.
|
|
Onboard PID
|
It realizes process-controlled closed loop control system easily.
|
|
Automatic voltage
regulation (AVR)
|
It can keep constant output voltage automatically when the mains voltage changes.
|
|
Overvoltage/
Overcurrent stall
contro
|
The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/overcurrent.
|
|
Quick current limiting
|
Maximize overcurrent failure and protect the frequency converter in normal operation
|
|
Torque limit and
control
|
It can limit the torque automatically and prevent frequent over current tripping during the running process.
Torque control can be implemented in the CLVC mode.
|
|
Individualized functions
|
High performance
|
Control of asynchronous motor and synchronous motor are implemented through the high-performance current vector control technology.
|
|
Power dip ride
through
|
The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time.
|
|
Rapid current limit
|
It helps to avoid frequent overcurrent faults of the AC drive.
|
|
Timing control
|
Time range: 0.0–6500.0 minutes
|
|
Multi-motor
switchover
|
Four motors can be switched over via four groups of motor parameters.
|
|
Bus support
|
Support field bus: Modbus
|
|
Motor overheat
protection
|
The optional I/O extension card enables AI3 to receive the motor temperature sensor input (PT100, PT1000) so as to realize motor overheat protection.
|
|
Multiple encoder
types
|
Support difference, open collector and rotary transformer
|
|
Operation
|
Command source
|
Operation panel, control terminal and serial communication port are given
Switch in various methods
|
|
Frequency source
|
Various frequency sources: digital reference, analog voltage reference, analog current reference, pulse reference and serial port reference. The switching can be conducted in various methods
|
|
Auxiliary frequency source
|
10 kinds of auxiliary frequency source. The auxiliary frequency jog and frequency synthesis can be achieved flexibly
|
|
Input terminal
|
Standards:
7 digital input terminals, among which one support maximum high-speed pulse input of 100kHz
2 analog input terminals, among which one only supports voltage input of 0 ~10V and the other supports voltage input of 0 ~10V or current input of 4 ~20mA
Expansion capability:
3 digital input terminals
1 analog input terminal, which supports voltage input of -10V ~10V and supports PT100/PT1000
|
|
Operation
|
Output terminal
|
Standards:
1 high-speed pulse output terminal (The open collector type is optional), supporting 0~100kHz square signal output
1 digital output terminal
1 relay output terminal
1 analog output terminal, supporting current outpout of 0~20mA or voltage output of 0~10V
Expansion capability:
1 digital output terminal
1 relay output terminal
1 analog output terminal, supporting current output of 0~20mA or voltage output of 0~10V
|
|
Display and keyboard operation
|
LED display
|
Display the parameter
|
|
Key lock and function selection
|
Realize partial or all key lock and define the action range of some keys to prevent misoperation
|
|
Protection function
|
Short circuit test of electrified motor, input/output default phase protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, overload protection, etc.
|
|
Options
|
IO expansion card, differential input PG card, OC input PG card and rotary transformer PG card.
|
|
Environment
|
Service site
|
Indoor, free from direct sunshine, no dust, corrosive gas, combustible gas, oil fog, water vapor, drip or salt, etc.
|
|
Altitude
|
Less than 1,000m
|
|
Ambient temperature
|
-10℃~ +40℃ (Please use the equipment by derating at ambient temperature of 40℃~50 ℃)
|
|
Humidity
|
Less than 95%RH, no water condensation
|
|
Vibration
|
Less than 5.9m/s2(0.6g)
|
|
Storage temperature
|
-20℃~ +60℃
|
|
IP grade
|
IP20
|
|
Pollution level
|
PD2
|
|
Power distribution system
|
TN , TT
|